Mains connection | |
Voltage and power range | 1-phase, 200 to 240 V + 10% 0.37 to 2.2 kW (0.5 to 3 hp) 3-phase, 200 to 240 V + 10% 0.37 to 2.2 kW (0.5 to 3 hp) 3-phase, 380 to 480 V + 10% 0.37 to 4 kW (0.5 to 5 hp) |
Frequency | 48 to 63 Hz |
Motor connection | |
Voltage | 3-phase, from 0 to Usupply |
Frequency | 0 to 500 Hz |
Continuous loading capability (constant torque at a max. ambient temperature of 40oC) | Rated output current I2N |
Overload capability (at a max. ambient temperature of 40 oC) | At heavy duty use 1.5 x I2Nfor 1 minute every 10 minutes At start 1.8 x I2N for 2 s |
Switching frequency Default Selectable |
4 to 16 kHz with 4 kHz steps |
Acceleration time | 0.1 to 1800 s |
Deceleration time | 0.1 to 1800 s |
Braking | Built-in brake chopper as standard |
Motor control method | Scalar U/f |
Environmental limits | |
Ambient temperature | -10 to 40 oC (14 to 104oF), no frost allowed, 50 °C (122 oF) with 10% derating |
Altitude Output current | Rated current available at 0 to 1000 m (0 to 3281 ft) reduced by 1% per 100 m (328 ft) over 1000 to 2000 m (3281 to 6562 ft) |
Relative humidity | Lower than 95% (without condensation) |
Degree of protection | IP20/Optional NEMA 1 enclosure |
Enclosure colour | NCS 1502-Y, RAL 9002, PMS 420 C |
Contamination levels Transportation Storage Operation | IEC 721-3-3 No conductive dust allowed Class 1C2 (chemical gases) Class 1S2 (solid particles) Class 2C2 (chemical gases) Class 2S2 (solid particles) Class 3C2 (chemical gases) Class 3S2 (solid particles) |
Chokes | |
AC input chokes | External option.For reducing THD in partial loads and to comply with EN 61000-3-2. |
AC output chokes | External option. To achieve longer motor cables. |
Programmable control connections | |
One analog input Voltage signal Current signal Potentiometer reference value Resolution Accuracy | 0 (2) to 10 V, Rin > 312 kΩ 0 (4) to 20 mA, Rin = 100 Ω 10 V + 1% max. 10 mA, R < 10 kΩ 0.1% + 2% |
Auxiliary voltage | 24 V DC + 10%, max. 200 mA |
Five digital inputs | 12 to 24 V DC with internal or external supply, PNP and NPN, pulse train 0 to 16 kHz |
Input impedance | 2.4 kΩ |
One relay output Type Maximum switching voltage Maximum switching current Maximum continuous current | NO + NC 250 V AC/30 V DC 0.5 A/30 V DC; 5 A/230 V AC 2 A rms |
Product compliance | |
Low voltage Directive 2006/95/EC with supplements Machinery Directive 2006/42/EC EMC Directive 2004/108/EC with supplements Quality assurance system ISO 9001 Environmental system ISO 14001 UL, cUL, CE, C-Tick and GOST R approvals RoHS compliant |
A-86, Okhla Industrial Area, Phase II, Near Rama Motors, Near Rama Motors, Near Rama Motors, New Delhi, Delhi, 110020, India